Produktoersjoch en gebrûk
ZW7A-40.5: CT is ynboud as ekstern, en de eksterne isolaasje is it fysike uterlik fan siliconenrubber of porslein.
Produktmodel en betsjutting
Wurkomstannichheden
Normale gebrûksbetingsten
in.Ambient lucht temperatuer, minimum -30 °, maksimum +40 °;de gemiddelde temperatuer mjitten binnen 24 oeren is net mear as 35 °;
b.De hichte is net mear as 1000m;
c.It fersmoargingsnivo fan 'e omlizzende loft mei net boppe nivo II wêze;
d.De omlizzende loft is net fansels fersmoarge troch stof, reek, corrosive of flammable gas, stoom of sâlt spray;
e.De dikte fan iis moat net mear as 20 mm;
f.De wynsnelheid is net mear as 34m/s;
g.De seismyske fissure is net mear as 8 graden;
h.Feuchte betingsten:
De gemiddelde wearde fan relative vochtigheid mjitten binnen 24h, net mear as 95%;
De gemiddelde wearde fan de wetterdamp druk mjitten binnen 24h net mear as 2.2kPa;
De gemiddelde moanlikse relative vochtigheid is net mear as 90%;
De gemiddelde moanlikse wetterdampdruk is net mear as 1.8kPa;
As de boppeneamde normale gebrûk betingsten wurde oertroffen, nim dan oerlis mei de fabrikant fan tefoaren, en spesifisearje asjebleaft by it bestellen;
Abnormale gebrûksbetingsten
Ynklusyf de ekstreme gebrûksomjouwing lykas hichte boppe 1000 meter, rappe temperatuerferoaring, iis boppe 20 mm, swiere fersmoarging, swiere kondensaasje, mildew, sân, stof, swiere kjeld, brânende waarmte, trilling, ynfloed, swing, ensfh., ûnderhannelje asjebleaft yn foarút by it bestellen.
Main Technyske Parameters Of Zw7 Series Products
Nee. | Beskriuwing | Ienheid | Data | ||
1 | Rated voltage | kV | 40,5 | ||
2 | 1 min Rated macht frekwinsje wjerstean spanning 1min | kV | 95 | ||
3 | Rated wjerljocht ympuls wjerstean spanning | kV | 185 | ||
4 | Rated frekwinsje | Hz | 50 | ||
5 | Rated hjoeddeistige | A | 630, 1250, 1600, 2000, 2500 | ||
6 | Rated koarte tiid wjerstean stroom | kA | 20 | 25 | 31.5 |
7 | Rated piek wjerstean stroom | 50 | 63 | 80 | |
8 | Rated koartsluting breaking current | 20 | 25 | 31.5 | |
9 | Rated koartsluting meitsjen stroom | 50 | 63 | 80 | |
10 | Rated koarte-circuit doer | s | 4 | ||
11 | DC komponint fan rated koartsluting breaking current |
| 51 | ||
12 | Pykwearde fan transient herstelspanning (TRV) | kV | 114 | ||
13 | Rated macht oanbod spanning fan sluten en iepenjen apparaten en auxiliary circuits | V | DC/AC 220V, DC/AC 110V | ||
14 | Rated bestjoeringssysteem folchoarder |
| O-0.3s-CO-15s-CO | ||
15 | Iepeningstiid | ms | 20-50 | ||
16 | Slutingstiid | 30-80 | |||
17 | DC-tiidkonstante fan nominearre koartslutingsstroom | 45 | |||
18 | Rated kabel opladen breaking current | A | 50 | ||
19 | Service libben |
| E2-C2-M2 (10000) | ||
20 | Rated koarte-circuit breaking hjoeddeistige breaking tiden | Times | 20 |
Assembly Adjustment Parameter Tabel Of Zw7 Series Products
Nee. | Beskriuwing | Ienheid | Data |
1 | Kontakt iepening ôfstân | mm | 20±2 |
2 | Kontakt stroke | 4±1 | |
3 | Gemiddelde slutingssnelheid (mjitkontakt krekt foar it sluten oant 10 mm foar it sluten) | m/s | 0,8±0,3 |
4 | Gemiddelde iepeningssnelheid (mjitkontakt is gewoan ferdield op 10 mm útinoar) | 1,6±0,3 | |
5 | Bounce tiid fan kontakt sluten | ms | ≤5 |
6 | Bounce tiid fan kontakt sluten | ≤2 | |
7 | Trijepoal kontakt iepening yn ferskillende perioaden | ≤2 | |
8 | Main circuit ferset fan elke peal | μΩ | ≤100 (Sûnder ynstrumint transformator) |
9 | Opmerking: De boppesteande parameters ferwize nei de nominearre wurkspanning |
Ynstallaasje Ofmjittings
Op in hichte fan 1000 meter (sintraal ôfstân fan 710 mm), in hichte fan 2000 meter (sintrumôfstân fan 780), en in hichte fan 3000 meter (sintraal ôfstân fan 850), de totale ôfmjittings fan de circuit breaker binne as folget:
Op in hichte fan 4000 meter (sintrumôfstân 920), op 5000 meter (sintrum ôfstân 1000) meter, de totale ôfmjittings fan de circuit breaker binne as folget: